Schneider TeSys D contactor LC1D12G7

Schneider TeSys D contactor LC1D12G7

Model No.︰TeSys D

Brand Name︰Schneider

Country of Origin︰China

Unit Price︰US $ 1 / pc

Minimum Order︰50 pc

Inquire Now

Product Description

Main

Range  TeSys
Product name  TeSys D
Product or component type  Contactor
Device short name  LC1D

Contactor application 

Motor control
Resistive load
Utilisation category  AC-3
AC-4
AC-1
Poles description  3P
Pole contact composition  3 NO
[Ue] rated operational voltage  <= 300 V DC for power circuit
<= 690 V AC 25...400 Hz for power circuit
[Ie] rated operational current  12 A (<= 60 °C) at <= 440 V AC AC-3 for power circuit
25 A (<= 60 °C) at <= 440 V AC AC-1 for power circuit
Motor power kW  7.5 kW at 500 V AC 50/60 Hz AC-3
7.5 kW at 660...690 V AC 50/60 Hz AC-3
5.5 kW at 380...400 V AC 50/60 Hz AC-3
5.5 kW at 415...440 V AC 50/60 Hz AC-3
3 kW at 220...230 V AC 50/60 Hz AC-3
3.7 kW at 400 V AC 50/60 Hz AC-4
Motor power hp  2 hp at 230/240 V AC 50/60 Hz for 1 phase motors
3 hp at 200/208 V AC 50/60 Hz for 3 phases motors
3 hp at 230/240 V AC 50/60 Hz for 3 phases motors
7.5 hp at 460/480 V AC 50/60 Hz for 3 phases motors
10 hp at 575/600 V AC 50/60 Hz for 3 phases motors
0.5 hp at 115 V AC 50/60 Hz for 1 phase motors
Control circuit type  AC 50/60 Hz
[Uc] control circuit voltage  120 V AC 50/60 Hz
Auxiliary contact composition  1 NO + 1 NC
[Uimp] rated impulse withstand voltage  6 kV conforming to IEC 60947
Overvoltage category  III
[Ith] conventional free air thermal current 25 A at <= 60 °C for power circuit
10 A at <= 60 °C for signalling circuit
Irms rated making capacity  250 A at 440 V for power circuit conforming to IEC 60947
140 A AC for signalling circuit conforming to IEC 60947-5-1
250 A DC for signalling circuit conforming to IEC 60947-5-1
Rated breaking capacity  250 A at 440 V for power circuit conforming to IEC 60947
[Icw] rated short-time withstand current  105 A <= 40 °C 10 s power circuit
210 A <= 40 °C 1 s power circuit
30 A <= 40 °C 10 min power circuit
61 A <= 40 °C 1 min power circuit
100 A 1 s signalling circuit
120 A 500 ms signalling circuit
140 A 100 ms signalling circuit
Associated fuse rating  25 A gG at <= 690 V coordination type 2 for power circuit
40 A gG at <= 690 V coordination type 1 for power circuit
10 A gG for signalling circuit conforming to IEC 60947-5-1
Average impedance  2.5 mOhm at 50 Hz - Ith 25 A for power circuit
[Ui] rated insulation voltage  600 V for power circuit certifications CSA
600 V for power circuit certifications UL
690 V for power circuit conforming to IEC 60947-4-1
690 V for signalling circuit conforming to IEC 60947-1
600 V for signalling circuit certifications CSA
600 V for signalling circuit certifications UL
Electrical durability  2 Mcycles 12 A AC-3 at Ue <= 440 V
0.8 Mcycles 25 A AC-1 at Ue <= 440 V
Power dissipation per pole  0.36 W AC-3
1.56 W AC-1
Protective cover  With
Mounting support  Rail
Plate
Standards  CSA C22.2 No 14
EN 60947-4-1
EN 60947-5-1
IEC 60947-4-1
IEC 60947-5-1
UL 508
Product certifications  UL
LROS (Lloyds register of shipping)
DNV
BV
CCC
GOST
CSA
GL
RINA
Connections - terminals  Control circuit : screw clamp terminals 2 cable(s) 1...2.5 mm² - cable stiffness: flexible - with cable
end
Power circuit : screw clamp terminals 1 cable(s) 1...4 mm² - cable stiffness: flexible - with cable end
Control circuit : screw clamp terminals 1 cable(s) 1...4 mm² - cable stiffness: flexible - without cable
end
Control circuit : screw clamp terminals 2 cable(s) 1...4 mm² - cable stiffness: flexible - without cable
end
Control circuit : screw clamp terminals 1 cable(s) 1...4 mm² - cable stiffness: flexible - with cable end
Control circuit : screw clamp terminals 1 cable(s) 1...4 mm² - cable stiffness: solid - without cable end
Control circuit : screw clamp terminals 2 cable(s) 1...4 mm² - cable stiffness: solid - without cable end
Power circuit : screw clamp terminals 1 cable(s) 1...4 mm² - cable stiffness: flexible - without cable
end
Power circuit : screw clamp terminals 2 cable(s) 1...4 mm² - cable stiffness: flexible - without cable
end
Power circuit : screw clamp terminals 2 cable(s) 1...2.5 mm² - cable stiffness: flexible - with cable end
Power circuit : screw clamp terminals 1 cable(s) 1...4 mm² - cable stiffness: solid - without cable end
Power circuit : screw clamp terminals 2 cable(s) 1...4 mm² - cable stiffness: solid - without cable end
Tightening torque  Power circuit : 1.7 N.m - on screw clamp terminals - with screwdriver flat Ø 6 mm
Power circuit : 1.7 N.m - on screw clamp terminals - with screwdriver Philips No 2
Control circuit : 1.7 N.m - on screw clamp terminals - with screwdriver flat Ø 6 mm
Control circuit : 1.7 N.m - on screw clamp terminals - with screwdriver Philips No 2
Operating time  4...19 ms opening
12...22 ms closing
Safety reliability level 

B10d = 1369863 cycles contactor with nominal load conforming to EN/ISO 13849-1

B10d = 20000000 cycles contactor with mechanical load conforming to EN/ISO 13849-1

Mechanical durability  15 Mcycles
Operating rate  3600 cyc/h at <= 60 °C

 If you need more detailed parameter,

pls feel free contact us at:

Skype: shu.vicky2

Our Company website: http://www.BMingPower.com

Payment Terms︰ TT