Range |
TeSys |
Product name |
TeSys D |
Product or component type |
Contactor |
Device short name |
LC1D |
Contactor application
|
Motor control
Resistive load |
Utilisation category |
AC-3
AC-4
AC-1 |
Poles description |
3P |
Pole contact composition |
3 NO |
[Ue] rated operational voltage |
<= 300 V DC for power circuit
<= 690 V AC 25...400 Hz for power circuit |
[Ie] rated operational current |
12 A (<= 60 °C) at <= 440 V AC AC-3 for power circuit
25 A (<= 60 °C) at <= 440 V AC AC-1 for power circuit |
Motor power kW |
7.5 kW at 500 V AC 50/60 Hz AC-3
7.5 kW at 660...690 V AC 50/60 Hz AC-3
5.5 kW at 380...400 V AC 50/60 Hz AC-3
5.5 kW at 415...440 V AC 50/60 Hz AC-3
3 kW at 220...230 V AC 50/60 Hz AC-3
3.7 kW at 400 V AC 50/60 Hz AC-4 |
Motor power hp |
2 hp at 230/240 V AC 50/60 Hz for 1 phase motors
3 hp at 200/208 V AC 50/60 Hz for 3 phases motors
3 hp at 230/240 V AC 50/60 Hz for 3 phases motors
7.5 hp at 460/480 V AC 50/60 Hz for 3 phases motors
10 hp at 575/600 V AC 50/60 Hz for 3 phases motors
0.5 hp at 115 V AC 50/60 Hz for 1 phase motors |
Control circuit type |
AC 50/60 Hz |
[Uc] control circuit voltage |
120 V AC 50/60 Hz |
Auxiliary contact composition |
1 NO + 1 NC |
[Uimp] rated impulse withstand voltage |
6 kV conforming to IEC 60947 |
Overvoltage category |
III |
[Ith] conventional free air thermal current |
25 A at <= 60 °C for power circuit
10 A at <= 60 °C for signalling circuit |
Irms rated making capacity |
250 A at 440 V for power circuit conforming to IEC 60947
140 A AC for signalling circuit conforming to IEC 60947-5-1
250 A DC for signalling circuit conforming to IEC 60947-5-1 |
Rated breaking capacity |
250 A at 440 V for power circuit conforming to IEC 60947 |
[Icw] rated short-time withstand current |
105 A <= 40 °C 10 s power circuit
210 A <= 40 °C 1 s power circuit
30 A <= 40 °C 10 min power circuit
61 A <= 40 °C 1 min power circuit
100 A 1 s signalling circuit
120 A 500 ms signalling circuit
140 A 100 ms signalling circuit |
Associated fuse rating |
25 A gG at <= 690 V coordination type 2 for power circuit
40 A gG at <= 690 V coordination type 1 for power circuit
10 A gG for signalling circuit conforming to IEC 60947-5-1 |
Average impedance |
2.5 mOhm at 50 Hz - Ith 25 A for power circuit |
[Ui] rated insulation voltage |
600 V for power circuit certifications CSA
600 V for power circuit certifications UL
690 V for power circuit conforming to IEC 60947-4-1
690 V for signalling circuit conforming to IEC 60947-1
600 V for signalling circuit certifications CSA
600 V for signalling circuit certifications UL |
Electrical durability |
2 Mcycles 12 A AC-3 at Ue <= 440 V
0.8 Mcycles 25 A AC-1 at Ue <= 440 V |
Power dissipation per pole |
0.36 W AC-3
1.56 W AC-1 |
Protective cover |
With |
Mounting support |
Rail
Plate |
Standards |
CSA C22.2 No 14
EN 60947-4-1
EN 60947-5-1
IEC 60947-4-1
IEC 60947-5-1
UL 508 |
Product certifications |
UL
LROS (Lloyds register of shipping)
DNV
BV
CCC
GOST
CSA
GL
RINA |
Connections - terminals |
Control circuit : screw clamp terminals 2 cable(s) 1...2.5 mm² - cable stiffness: flexible - with cable
end
Power circuit : screw clamp terminals 1 cable(s) 1...4 mm² - cable stiffness: flexible - with cable end
Control circuit : screw clamp terminals 1 cable(s) 1...4 mm² - cable stiffness: flexible - without cable
end
Control circuit : screw clamp terminals 2 cable(s) 1...4 mm² - cable stiffness: flexible - without cable
end
Control circuit : screw clamp terminals 1 cable(s) 1...4 mm² - cable stiffness: flexible - with cable end
Control circuit : screw clamp terminals 1 cable(s) 1...4 mm² - cable stiffness: solid - without cable end
Control circuit : screw clamp terminals 2 cable(s) 1...4 mm² - cable stiffness: solid - without cable end
Power circuit : screw clamp terminals 1 cable(s) 1...4 mm² - cable stiffness: flexible - without cable
end
Power circuit : screw clamp terminals 2 cable(s) 1...4 mm² - cable stiffness: flexible - without cable
end
Power circuit : screw clamp terminals 2 cable(s) 1...2.5 mm² - cable stiffness: flexible - with cable end
Power circuit : screw clamp terminals 1 cable(s) 1...4 mm² - cable stiffness: solid - without cable end
Power circuit : screw clamp terminals 2 cable(s) 1...4 mm² - cable stiffness: solid - without cable end |
Tightening torque |
Power circuit : 1.7 N.m - on screw clamp terminals - with screwdriver flat Ø 6 mm
Power circuit : 1.7 N.m - on screw clamp terminals - with screwdriver Philips No 2
Control circuit : 1.7 N.m - on screw clamp terminals - with screwdriver flat Ø 6 mm
Control circuit : 1.7 N.m - on screw clamp terminals - with screwdriver Philips No 2 |
Operating time |
4...19 ms opening
12...22 ms closing |
Safety reliability level |
B10d = 1369863 cycles contactor with nominal load conforming to EN/ISO 13849-1
B10d = 20000000 cycles contactor with mechanical load conforming to EN/ISO 13849-1
|
Mechanical durability |
15 Mcycles |
Operating rate |
3600 cyc/h at <= 60 °C |